Assembly clean room installation
**Clean Room Assembly Installation**
Article 2.5.1: The installation of the assembled clean room should be carried out after the completion of all interior decoration works. The indoor space must be kept clean and free from dust. Throughout the construction and installation process, all parts and areas should be regularly cleaned and wiped to maintain a high level of cleanliness.
Article 2.5.2: During the installation process, the attachment of hanging structures, anchors, and other components to the main structure, floor, and ceiling should be securely fixed first to ensure stability and safety.
Article 2.5.3: The floor surface must be smooth, with unevenness not exceeding 0.1%. When installing the wall panels, special attention should be given to the sealing at the junction between the floor and vertical walls, especially when using coil or coating finishes.
Article 2.5.4: Before installing the wall panels, wiring should be carefully laid out, and corners should be vertically aligned to prevent panel twisting. The vertical deviation of the panels must not exceed 0.2%.
Article 2.5.5: The ceiling should be arched in the direction of the room’s width to ensure it remains flat under load. The perimeter of the ceiling should be tightly connected to the walls for a seamless finish.
Article 2.5.6: During installation, the plastic protective film on the surface of the wall panels must not be removed. Any impact or foot traffic on the panels should be strictly avoided to prevent damage.
Article 2.5.7: All fittings and materials should be stored in a clean and dry environment, supported by a retaining structure and placed flat on a moisture barrier film to protect them from damage.
Article 2.5.8: Unpacking and opening of fittings and materials must be done in a clean environment. Each component should be thoroughly inspected for performance and integrity. Any damaged or non-conforming parts must be rejected immediately.
Article 2.5.9: Before applying surface coatings or sealants, the surfaces and grooves must be thoroughly cleaned to remove any impurities or oil. This ensures strong adhesion and prevents peeling or dust accumulation.
Article 2.5.10: All gaps during the assembly of the clean room must be sealed properly using appropriate sealant to maintain the integrity of the clean environment.
---
The **BHC-1300IIA/B3 Biological Clean Safety Cabinet** is an essential piece of equipment in modern microbiology laboratories, particularly where operator protection is critical. It is widely used in medical, pharmaceutical, and research settings to provide a sterile, dust-free, and safe working environment for bacterial cultures.
**Key Features:**
1. Constant airflow with 100% exhaust and negative pressure flow.
2. Adjustable glass door that can be positioned freely, with a height limit alarm for safety.
3. Integrated power outlet in the work area.
4. High-efficiency filters (HEPA) that filter particles, fumes, and microorganisms with over 99.999% efficiency.
5. Constructed from high-quality 304 stainless steel, ensuring a smooth, seamless, and easy-to-clean surface.
6. Controlled via an LED LCD panel for user-friendly operation.
7. Equipped with alarms for high-efficiency filter failure and airflow issues.
8. Provides excellent illumination and low noise levels for a comfortable working environment.
**Specifications:**
- **Cleanliness Level:** 100 @ ≥0.5μm (US Federal 209E)
- **Colony Count:** <0.5 pcs/dish (90mm culture plate)
- **Noise Level:** ≤62 dB(A)
- **Airflow Speed:** 0.38 ± 0.025 m/s
- **Vibration:** <5 μm (X, Y, Z directions)
- **Illumination:** ≥300 LX
- **Front Suction Airspeed:** 0.55 ± 0.025 m/s
- **Gas Flow Rate:** ≤10â»â¶ m/s (under 500 Pa pressure)
- **Power Supply:** AC, single phase 220V/50Hz
- **Maximum Power Consumption:** 600W
- **Weight:** 350 kg
- **Working Dimensions:** 1340 × 650 × 600 mm
- **Overall Dimensions:** 1540 × 800 × 1950 mm
- **High-Efficiency Filter Size:** 1335 × 600 × 38 × 1 mm
- **UV / Fluorescent Lamps:** 16W * 2 / 15W * 2